GEN-SET
TECHNICAL SPECIFICATION
Cat Olympian model GEH 175 diesel generating set rated at 175 KVA, (132 kW at 0.8 pf), 3 phase, 480/277 volts, 60 Hz, 1800 RPM at NTP conditions.
Powered by a Perkins, 6 cylinder, turbocharged diesel engine with directly coupled Newage Stamford brushless alternator.
Each machine will be built to a complete specification including:
- Heavy duty fabricated steel skid type baseframe with anti-vibration mounting pads.
- Electric starting system with heavy duty lead acid type starting batteries and battery charging system.
- High capacity air, fuel and lubricating oil filters.
- Fuel feed and return lines from engine to 8 hour capacity baseframe fuel tank.
- Industrial exhaust silencer system.
- Electronic engine speed governor.
- Automatic engine shutdown protection equipment with LED indicator for low oil pressure, high engine temperature, low coolant level, overspeed, and fail to start.
- Set mounted 2000 series autostart control and instrument cubicle containing voltmeter with phase selection switch, ammeter with phase selection switch. dual scale frequency/tachometer, water temperature gauge, oil pressure gauge, battery, voltmeter, hours run counter, 3 attempt starting timer, mode selector switch run/off/auto, emergency stop button, lamp test/reset button, terminals for remote start, remote emergency stop and common alarm signal.
- Set mounted circuit breaker cubicle containing suitably rated 3 pole moulded case circuit breaker.
- Instruction manuals and electrical wiring diagrams.
|